General
YCM7 Series circuit breaker were developed according to the demand of domestic and international market as well as features of like products. Its rated insulation voltage up to 690V is suitable for AC 50Hz distribution network circuit whose rated operation voltage is up to 690V with rated operation current up to 300A. lt can distribute power, protect the circuit and spare the power supply devices from overload, short circuit and under voltage. At the same time, it can Protect the motor from overload, short circuit and under voltage. This series circuit breake features small volume, high breaking capacity and short arcing. It can be installed vertically and also installed horizontally. It complies with standards of IEC60947-2.
Feature
- Miniaturization The volume of products are miniaturized. For example, 125 is the shell upgraded type of 63, that can satisfy the personal requirement for size.
- The consistent size They have same shell grade and size but different breaking capacities(C,S,M)出 well as functions(air,leakage of power)
- The proper setting of parameter This series can modify long delay time of inverse-time limit when it comes to overloading and parameter of short ciecuit instantaneous operation. The user can sets the protection features by himself to realize a more proper distribution in network circuit.
Enviroment and Conditions of Installation
- Altitude below 2000m
- Surrounding medium temperature below +40 degrees above -Sdegree
- Humidity resistance
- Bacteria-resistance
- Nuelear radiation resistance
- Max lean degree is 22.5 degree.
- Can operate normally when it comes to vibrataion of ship.
- Can operate normally when it comes to earthquake(4g).
- The medium should be no risk of blasting and can’t erode the metal and damage insulating gas as well as conductive dust.
- Work in the places where is no rain and snow.
Hãy là người đầu tiên nhận xét “YCM7”